This article refers to G&L PiC application note AN000021 and provides PiC900 scan times.
The following scan rates were measured by inserting 1024 bytes of logic that consists of contacts and coils, and measuring the resultant scan rate with a logic analyzer. Actual application scan rates may differ due to use of servos, user functions, etc..
|
Processor Model |
Scan Rate (Microseconds per K) |
|---|---|
|
PiC900 Standard |
384 |
|
PiC900 Turbo |
192 |
|
PiC900 Turbo² |
78 |
|
PiC90 Standard |
384 |
|
PiC9 / PiC90 Turbo |
192 |
|
PiC900 Model 911 |
288 |
|
PiC900 Model 912 Turbo |
144 |
|
PiC900 Model 943 Turbo² |
66 |
|
PiC900 Model 945 Turbo³ |
26 |