Start Hiperterminal:
with no response;
„\“ type until the command is accepted, then switch over with
„\ 0“ to the master;
type SCANX and
Prompt „-->“ wait;
Now communication is possible.
Kollmorgen Destek Ağı
The below represents frequent questions our support, engineering and sales teams have been asked over the years. If you have a question, please submit our contact us form to reach our application engineering team.
Start Hiperterminal:
with no response;
„\“ type until the command is accepted, then switch over with
„\ 0“ to the master;
type SCANX and
Prompt „-->“ wait;
Now communication is possible.
See the page Indexing
MLGQ = 12 * L{mH} * DIPEAK {A} / 1000
KTN 0.6
Example:
S603 --> Dipeak 6A
L=3mH - Motor inductance
MLGQ = 12 * L * DIPEAK / 1000 = 0.216
KTN 0.6
Leave all other values unchanged.
Set BUSP1 to 1 and finalize the configuration change with SAVE and COLDSTART.
Background: Bit 30 (COB-ID Setting for Tx-PDO) is supervised since Firmware 2.51. The amplifier sets the bit and expects the COB identifier is written with set bit 30, too (means: no RTR request of TX-PDOs is possible).
If bit 0 is set to 1, then bit 30 is not supervised any more.
The incremental current actual value (iq, q component) of the current controller is triggered two times within 62,5µs and the values are added but the average is not determined.
Units: ±3280 = ±DIPEAK in IncrAmpere?.
DIPEAK = device peak current
Pulse length < 100µs, off-time > 200ms. See page Test Pulse.
Yes. The current tools work with Windows Vista and Windows 7 without restrictions.
Yes. With the help of pole number setting. Refer to page Tuning - High Frequency Spindles S300-S700.
This can be selected on the screen page "Motion Task Parameters". Refer to page Motion Task Series.
P01: 1A power stage, mains supply voltage switched on, power stage disabled
E01: 1A power stage, mains supply voltage switched on, power stage enabled
-S-: STO Enable input is not connected or no 24V signal is applied
Refer to page LED Display Codes S300-S700.
Yes, you can activate a password protection. Refer to page Password Protection.
Fault in the power output stage. Can also be triggered by a wrong or faulty motor cable, if the screen of the motor cable is not connected or if the motor is feaulty. Refer to page Error Message F14.
Possible reasons:
Incremental signals (AquadB): processing time in the servo amplifier (FPGA) are in "ns" range. Slave reaction time ±62,5µs (current control task).
The servo amplifiers use position registers to define cams. The status of the registers are sent as cams to one or two digital outputs by a predefined function. Refer to page Setup of Camming S300-S700 or Setup of Camming S400-S600. You can define up to 8 cams for a digital output with S300/S700.
Low rotor inertia is the source for this problem, ironless linear motors show a similar behavior.
Solution for drives with S300/S700 servo amplifiers:
Refer to page External zero pulse
Yes, either sequential with the function InxMODE=30 or with parallel switch over of two predefined parameter sets. Refer to page Switching over parameter sets.
Bode Plot is a process to analyze frequency behavior of the drive. See pages Tuning - Built in Frequency Analysis and Bode Diagram
Yes, that's possible with S300 and S700. See page Operating DC motors S300-S700.