getting the following error when cold starting an MMC smart drive rack 0 slot 2 test 0 error 3

0 votes
+ vote
Vote up!
The control diagnostics indicate a failure in
rack 0 slot 2 test 0 error 3

Customer had battery failure

How do I fix this
I have reinstalled the firmware and program

now stuck at this message
cant see drives in maintenance mode
using serial cable
 
0 Comments

1 Answer

0 votes
+ vote
Vote up!

Hello,

 

Try clearing the application memory in the MMC controller and reloading your ladder program.  The rror code you are receiving from the MMC controller's diagnostics is not a listed fault.

 

image

 

image

image

Thanks,

0 Comments